J. Kor. Inst. Fire Sci. Eng. Search

CLOSE


Journal of Korean Institute of Fire Science and Engineering 1991;5(1):29-36.
Published online January 31, 1991.
고온수열된 무기질단열재의 물성변화에 관한 실험적 연구
김봉주김태용오창희
1한양대학교 대학원2한양대3한양대
An Experimental Study on the Property Transformation for High-Heated Inorganic Insulation
Abstract
The purpose of this study is to understand the variations of the properties of matters according to the heated temperature of inorganic insulation. As a result, form the variation of heat conductivity and maintaining from of insulation, the range of reusable heated temperature of inorganic insulation is as follows. Glass wool : $400^{circ}C$, Rock wool : $600^{circ}C$, Perlite : $800^{circ}C$.


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2024 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next