J. Kor. Inst. Fire Sci. Eng. Search

CLOSE


Journal of Korean Institute of Fire Science and Engineering 2011;25(3):63-71.
Published online June 30, 2011.
가연물 접촉에 따른 전기히터의 화재위험성에 관한 실험적 연구
이성룡
중앙소방학교 소방과학연구실
An Experimental Study on the Fire Risk of Electric Heaters According to Contact of Flammable Materials
Lee Sung-Ryong
요약
본 연구에서는 대표적인 계절용기기인 전기히터에 대하여 발화위험성을 평가하였다. 실험에는 2종류의 전기히터가 사용되었다. 전기히터 가동 시 히터 표면 및 주변의 온도변화를 측정하였으며, 내부 비파괴검사를 통하여 전기히터 내부구조를 파악하였다. 전기히터 화재원인 중 가장 높은 비율을 차지하는 가연물 근접방치에 의한 화재위험성을 평가하였다. 또한 전도 안전스위치 오작동에 의한 발화위험성을 평가하였다. 정상작동 시 전기히터 발열제 주위에서 온도가 $80^{circ}C$ 이하로 유지되었다. 전기히터 가동 중 가연물 낙하 등으로 인하여 히터를 덮거나 안전장치(전도안전스위치, 과열방지장치)의 오작동 등에 의해 발화위험성이 상존하고 있다.
Abstract
In this study, it was evaluated the fire risk of an electric heater as representative seasonal appliances. Two type of electric heaters were used in experiments. When electric heaters were operated, temperature variation was measured around the heater. Internal structure was understood by Nondestructive inspection. It was evaluated the tire risk of electric heaters, when flammable materials were positioned ear a heater. It was also estimated the probability of a tire in case of malfunction of a safety tip-over witch. When a heater was operated in a normal condition, temperature was maintained under $80^{circ}C$ around the heater. The possibility of a fire is very high, when a heater is covered with flammable materials or malfunction of safety parts (safety tip-over switch, anti-overheating devices).
Key Words: Electric heater, Fire risk, Flammable material, Nondestructive inspection


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2024 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next