J. Kor. Inst. Fire Sci. Eng. Search

CLOSE


Fire Sci. Eng. > Volume 26(5); 2012 > Article
Journal of Korean Institute of Fire Science and Engineering 2012;26(5):92-98.
DOI: https://doi.org/10.7731/KIFSE.2012.26.5.092    Published online October 31, 2012.
초고층건물 샤프트의 수직구획이 연돌효과 및 급기가압 성능에 미치는 영향
김범규, 김학중, 여용주, 임채현, 박용환
1호서대학교 소방방재학과
2호서대학교 소방방재학과
3호서대학교 소방방재학과
4호서대학교 소방방재학과
5호서대학교 소방방재학과
The Influence of Zoning at Shafts of Super-tall Buildings on the Stack Effect and Stairwell Pressurization
Kim Beom-Kyue, Kim Hak-Jung, Yeo Yong-Ju, Leem Chae-Hyun, Park Yong-Hwan
1Dept. of Fire Protection and Disaster Prevention Engineering, Hoseo Univ.
2Dept. of Fire Protection and Disaster Prevention Engineering, Hoseo Univ.
3Dept. of Fire Protection and Disaster Prevention Engineering, Hoseo Univ.
4Dept. of Fire Protection and Disaster Prevention Engineering, Hoseo Univ.
5Dept. of Fire Protection and Disaster Prevention Engineering, Hoseo Univ.
요약
최근 개정된 초고층건물 특별법에서는 피난안전구역을 최소 30개층 마다 설정함과 동시에 계단실을 수직구획 하도록 규정하고 있다. 이에 본 연구에서는 중앙코아 방식의 80층 초고층건물 계단실 수직구획이 연돌효과 및 계단실 급기가압 성능에 미치는 영향을 시뮬레이션 해석을 통해 분석하였다. 해석결과, 계단실 수직구획이 없는 경우 연돌효과로 인해 최대 차압 250 Pa 이상이 발생하였으며, 계단실만 수직구획한 경우에는 10 Pa 정도만 감소하였으나 계단실과 승강기의 승강로를 동시에 수직구획한 경우 최대차압이 약 125 Pa로 낮아져 연돌효과가 약 50 % 감소하였다. 또한, 계단실을 급기가압 할 경우 계단실온도가 실내온도와 외기온도 차이의 약 1/2일 때가 소요급기풍량 측면에서 가장 효율적인 것으로 예측되었다.
Abstract
This study analyzed the effect of zoning on the distribution of pressure differentials caused by stack effect and air pressurization in a center core type of 80 story super-tall building. The results showed that maximum pressure difference more than 250 Pa can be generated by stack effect without zoning. Zoning of stairwell only resulted in 10 Pa reduction of maximum pressure difference, however, zoning of both stairwell and EV shaft especially at the same floor revealed 50 % reduction in stack effect. It was also analysed that the minimum required air flow rate occurred when the stairwell temperature reached 50 % of temperature difference between indoor and outdoor.
Key Words: Zoning, Stack effect, Super-tall building, Stairwell pressurization, EV shaft


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next