Fire Sci. Eng. Search

CLOSE


Fire Sci. Eng. > Volume 28(2); 2014 > Article
Fire Science and Engineering 2014;28(2):54-63.
DOI: https://doi.org/10.7731/KIFSE.2014.28.2.054    Published online April 30, 2014.
UL 268 시험화원에 따른 CO센서의 화재감지센서로서의 적용성에 관한 연구
이춘하, 성완기, 이종화, 김형권, 지승욱, 김시국
1호서대학교 소방방재학과
2호서대학교 소방방재학과
3호남대학교 소방행정학과
4한국소방산업기술원
5(주)태산전자
6호서대학교 소방방재학과
A Study on the Adaptability of the CO Sensor as A Fire Detection Sensor According to the Test Fire Source of UL 268
Lee Chun-Ha, Sung Want-Ki, Lee Jong-Hwa, Kim Hyeong-Gweon, Jee Seung-Wook, Kim Si-Kuk
1Dept. of Fire and Disaster Protection Engineering, Hoseo Univ.
2Dept. of Fire and Disaster Protection Engineering, Hoseo Univ.
3Dept. of Fire Service Administration, Honam Univ.
4Korea Fire Institute of Industrial & Technology
5Tae San Electronics Co., Ltd.
6Dept. of Fire and Disaster Protection Engineering, Hoseo Univ.
요약
본 논문은 CO센서의 화재에 대한 감지특성을 분석 후 화재감지기로서의 적용성 판단을 하기 위한 논문이다. CO센서의 화재감지기로의 적용성을 판단하기 위해 UL 268에서 규정하고 있는 화재시험실과 유사한 규모의 화재실험장을 설계 제작하고, UL 268에서 제시된 화재시험기준에 준한 실화재실험을 실시하여 화원 종류에 따른 CO센서와 광전식연기감지기의 다양한 화원의 화재에서 발생하는 일산화탄소와 연기에 대한 감지특성을 측정하여 비교 분석하였다. 실험결과 종이화원 및 목재화원과 같이 불완전연소로 진행되는 초기화재에서 CO센서가 광전식연기감지기보다 약 2~3배 빠른 감지특성이 나타났다. 특히, 목재훈소화재에서 CO센서의 감지특성이 매우 우수한 것으로 나타났다.
Abstract
The purpose of this study is to test the adaptability of the CO sensor as a fire detector by analyzing its sensing characteristics on fire. In order to test the applicability, we designed and made a fire testing ground whose size is similar to that regulated by UL 268, carried out real fire tests suggested by UL 268, and conducted a comparison analysis on the sensing characteristics between the CO sensor and a photoelectric smoke detector by different types of fire source. The experiment result to the sensing characteristics of the CO sensor is about twice to three times faster than that of the photoelectric smoke detector, proceeding with incomplete combustion such as paper and wood fire source in the initial fire. Especially in case of wood smoldering fire, sensing characteristics of the CO sensor is very excellent.
Key Words: CO sensor, Fire detection sensor, Sensing characteristics, UL 268, Fire source


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next