Fire Science and Engineering 2014;28(6):52-57.
DOI: https://doi.org/10.7731/KIFSE.2014.28.6.052    Published online December 31, 2014.
가연물의 발열량 특성을 고려한 화재감식 적용방안에 관한 연구
강정기, 오진희, 유우준, 유홍선, 최돈묵
1대검찰청
2대검찰청
3한국소방산업기술원
4중앙대학교
5가천대학교
A Study on the Application Scheme of Fire Identification Considering the Heat Release Rate Characteristics of Inflammable Material
Kang Jung-Ki, Oh Jin-Hee, You Woo-Jun, Ryou Hong-Sun, Choi Don-Mook
1Supreme Prosecutors' Office
2Supreme Prosecutors' Office
3Korea Fire Institute of Industrial & Technology
4Dept. of Mechanical Engineering, Chung-Ang University
5Dept. of Fire & Disaster Protection Engineering Graduate School, Gachon Univ.
요약
본 연구는 건축 구조물의 방화 등으로 인해서 발생한 가연물의 연소현상을 분석하여 화재발생 시점을 예측하기 위한 기초 방안을 제시하였다. 이를 위해서 계단실 화재사고 사례로부터 가연물을 인터폰 개별현관기(이하 '인터폰'으로 표시)로 선정하고 룸코너시험기(room corner test equipment)에서 화재실험을 실시하여 시간 변화에 따른 발열량을 산출하였으며, 화재시뮬레이션 프로그램인 fire dynamics simulator (FDS)를 사용하여 화재성상 변화에 따라서 발화지점 하층부로 연기가 유입되는 시간을 비교하였다. 그 결과 가연물이 ABS 재질로 구성된 인터폰은 계단실 총 체적 공간 $291.3m^3$, 바닥면적 $23.3m^2$, 층간 높이 2.5 m인 경우 발화원의 열 유속 및 환경 조건에 따라서 최대 4.93배 정도 연기 유입 시간이 차이가 나는 것을 확인하였다. 본 연구는 가연물의 열화학적 특성 변화를 고려한 실험 자료를 해석모델에 적용하여 화재감식을 분석적으로 판단하는데 유용한 자료가 될 것으로 사료된다.
Abstract
The present study suggests the fundamental method for the prediction time of the fire origin by analyzing the combustion phenomenon of inflammable material in the building structure. The heat release rate (HRR) with time variant is evaluated for the interphone as a inflammable material, which is opted from the fire incidents in the stairwell. the fire dynamics simulator (FDS ver. 6.1) is applied in order to analyze the difference of the smoke inflow time to the downstair from the fire event area with various fire pattern. The results show that the maximum inflow time difference for the case of the interphone made from ABS materials is about 4.93 times with the input conditions of heat flux values and the environment in the FDS for the fixed stairwell which composed of total volume $291.3m^3$, floorage $23.3m^2$ and the height of each floor 2.5 m. This research can be practical information for the application method of simulation scheme with experimental data to the fire Identification.
Key Words: Fire identification, Heat release rate, Smoke inflow time, Inflammable material of ABS, Fire dynamics simulator


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next