정온식 열감지기의 응답시간지수 및 작동시간 |
류호철태순호이병곤 |
1충북대학교 대학원 산업안전공학과2서울산업대학 산업안전공학과3충북대학교 산업안전공학과 |
Response Time Index and Operation Time of Fixed Temperature Heat Detector |
|
|
|
Key Words:
정온식 열감지기, 시간상수, 응답시간지수, 작동시간, 작동온도 |
Abstract |
Fixed temperature heat detectors that respond to the heat generated in fire plume and alarm when the temperature reaches a specified point, give a great influences to the loss of life and property according to their reaction sensitivity. In this study, hot wind tunnel tests and compartment fire experiments were performed to investigate the response time and temperature of fixed temperature heat detector. As a result, simple equations were derived which can be predicted the response time and temperature of the fixed temperature heat detector for the ramp type fire. Also other useful data, such as the effective temperature, time constant, response time index(RTI) were obtained. |
|