Fire Sci. Eng. Search

CLOSE


Fire Sci. Eng. > Volume 32(6); 2018 > Article
Fire Science and Engineering 2018;32(6):7-14.
DOI: https://doi.org/10.7731/KIFSE.2018.32.6.007    Published online December 31, 2018.
FDS를 이용한 실규모 공연장 무대 내 화재 시 연기 거동 분석: 방화막 및 자연배출구 면적의 영향
김재한, 이치영, 정이규, 김동균
1부경대학교 소방공학과 대학원
2부경대학교 소방공학과
3한국해양수산연수원
4한국산업기술시험원
Analysis of Smoke Behavior in Fire within Real-scale Theater Using FDS: Influences of Fire Curtain and Natural Smoke Vent Area
Kim Jae Han, Lee Chi Young, Jeong Lee Gyu, Kim Duncan
1Dept. of Fire Protection Engineering, Pukyong Nat'l Univ.
2Dept. of Fire Protection Engineering, Pukyong Nat'l Univ.
3Korea Institute of Maritime and Fisheries Technology
4Korea Testing Laboratory
요약
본 연구에서는 방화막 및 자연배출구 면적이 공연장 무대 화재 시 연기 거동에 미치는 영향에 대해 Fire Dynamics Simulator (FDS)를 이용하여 전산시뮬레이션(Numerical simulation)을 수행하였다. 공연장의 무대 크기는 폭 31 m, 깊이 34 m, 높이 32 m로 설정하였고, 자연배출구 면적은 무대 바닥면적의 약 10%, 약 8%, 약 5%, 약 1%로 하였다. 방화막은 프로시니엄(Proscenium) 벽과 0.5 m 이격하여 설정하였다. 방화막과 자연배출구 면적은 객석으로의 연기유출, 자연배출구 및 프로시니엄 개구부를 통한 유입 및 유출 질량 유량에 지대한 영향을 미치는 것으로 관찰되었고, 동일한 자연배출구 면적 조건에서 방화막이 설치된 경우가 미설치된 경우에 비해 무대 내 압력이 더 낮은 것으로 나타났다.
Abstract
This study investigated numerically the influences of fire curtain and natural smoke vent area on smoke movement in the stage fire of a theater using FDS (Fire Dynamics Simulator). The dimension of the theater stage was 31 m in width, 34 m in depth, and 32 m in height. The area ratios between the natural smoke vent and stage were approximately 10%, 8%, 5%, and 1%. The gap distance between the fire curtain and proscenium wall was 0.5 m. The fire curtain and natural smoke vent area were observed to affect significantly the behavior of smoke movement to the auditorium and the mass flow rates of inflow and outflow through the natural smoke vent and proscenium opening. In addition, under the same natural smoke vent area, the pressure in the stage with a fire curtain was lower than that without a fire curtain.
Key Words: Fire curtain, Natural smoke vent area, Smoke movement, Theater fire, Fire dynamics simulator (FDS)


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2024 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next