J. Kor. Inst. Fire Sci. Eng. Search

CLOSE


Journal of Korean Institute of Fire Science and Engineering 2002;16(2):1-7.
Published online June 30, 2002.
고효율 LED를 이용한 유도등의 원격제어에 관한 연구
백동현홍석표
1경원전문대학 소방안전관리과2유신플랜테크 대표이사
A Study on the Remote Control for Exit Sign Using High Efficiency LED
요약
유도등은 일정한 조도를 가지고 상용전원에 의하여 항상 점등되어 있어야 함으로 전력소비 및 광원 교체등 경제적 손실과 관리상의 문제가 있게 된다. 본 논문은 이제까지 광원으로 사용하고 있던 형광등이나 백열전구 대신에 소비전력이 적은 고효율 발광다이오드를 사용하여 전력소비의 절감과, 점검시의 문제점을 개선하기 위해 원격제어가 가능한 새로운 유도등회로를 제안하고 실험한 것이다. 그 결과 원격제어 스위치에 의한 유도등 점검을 제어각의 범위에서 쉽게 제어할 수 있었으며 반응시간은 600〔$mu$s〕로 매우 빠르게 동작하였다. 또한 출력 상승시간(Rise time)과 하강시간(Fall time)은 최대 200〔ns〕로 예민하게 반응
Abstract
In the normally, exit sign is always lighting on status by the connected to normal electrical source. So, there are happened to rise of the economical cost such as power consumption, maintenances and repair replacement of lamp etc. This paper are study on the new exit sign circuits by using high efficiency LED that is available for remote control and reduceible to power consumption, maintenance cost by the way of compensation fluorescent and incandescent lamps. As a results on the study, exit sign lamp is capable of control and supervisory in trigger angle by the remote control switch, widely and easily. And then, the response time was very fast in 600〔$mu$s〕and also it can be find that the rising and fall time of oscillate circuit is maximum 200〔ns〕 as high sensitively. Finally, it obtain to the result that reducible of electrical power consumption and not required for replacement of lamp by using the high efficiency LED lighting source.
Key Words: Exit sign circuits, High efficiency LED, Remote control


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next