J. Kor. Inst. Fire Sci. Eng. Search

CLOSE


Journal of Korean Institute of Fire Science and Engineering 2004;18(4):27-34.
Published online December 31, 2004.
$CO_2$소화제 노즐과 벽간 거리의 영향
박찬수
목포해양대학교 기관공학부
The Effect of the Distance Between $CO_2$ Agent Nozzle and Wall
Park Chan-Su
요약
CO₂소화장치의 CO₂노즐과 방호공간 내 벽 사이의 거리변화에 따른 유동 및 CO₂질량전달효과를 분석하기 위하여 CO₂노즐과 후측 벽 사이의 거리를 변화시키면서 전산모이실험을 3차원 비정상상태로 수행하였다. 유동장과 CO₂소화제 농도장을 계산하였다. CO₂노즐과 후측 벽 사이의 거리 증가에 따라 다른 재 순환 유동형태와 벽면제트기류가 형성되었다. CO₂ 소화제 질량전달은 모든 경우에서 각 벽으로부터 방호공간의 중앙으로 일어나지만 CO₂소화제 노즐의 전 후 영역의 CO₂질량분율은 CO₂노즐과 벽 사이의 거리 증가에 따라 높거나 낮게 나타났다.
Abstract
We have conducted a numerical simulation under three-dimensional unsteady conditions in order to analyze the effect of flow and CO₂ mass transfer according to the distance between the CO₂ nozzle of CO₂ fire fighting system and the rear wall in a protection space. Flow fields and CO₂ concentration fields were measured. The different recirculation flow form and wall jet was developed according to increasing the distance between CO₂ nozzles and rear wall. In all the case, CO₂ mass transfer was generated toward the center of a protection space from each walls, but the CO₂ mass fraction of front and rear areas based on CO₂ nozzles showed higher or lower by increasing the distance between CO₂ nozzle and rear wall.
Key Words: CO₂ mass transfer, CO₂ nozzle, Wall jet
TOOLS
Share :
Facebook Twitter Linked In Google+ Line it
METRICS Graph View
  • 577 View
  • 5 Download
Related articles in Fire Sci. Eng.

The Effect of Fire Plume on the Characteristics of Air Flow and $CO_2$Extinguishant Transfer2002 December;16(4)



ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2025 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next