가솔린 화재의 소화를 위한 수분무의 특성에 관한 실험적 연구 |
장용재, 김명배, 김유 |
1한국기계연구원, 산업설비연구부2한국기계연구원, 산업설비연구부3충남대학교 |
Characteristics of Water Spray for Extinguishment of Gasoline Pool Fire |
jang Yong-Jae, Kim Myung-Bae, Kim Yu |
|
|
Key Words:
수분무, 소화, 가솔린 화재 |
Abstract |
This study discribes characteristics of water spray for extinguishment of gasoline fire. Experiments are carried out for the gasoline pool fire nth the atomizing nozzles. Droplet size, spray pressure, amount of water which reaches the flame base and velocity of water spray are measured to find extinguishment conditions. Air entrainment due to the water spray and extinguishing process of gasoline fire by water spray are visualized. Boundary conditions of water spray for extinguishment of gasoline pool fire is quantitatively shown. As the result of experiments, it is found that the velocity of entrainment air and sprayed water are almost same and the water droplets size having small diameter under 40$mu extrm{m}$ can not extinguish the fire because too small droplets does not reach the fuel surface. |
Key Words:
Water spray, Extinguishment, Gasoline pool fire |
|