J. Kor. Inst. Fire Sci. Eng. Search

CLOSE


Journal of Korean Institute of Fire Science and Engineering 2009;23(2):20-26.
Published online April 30, 2009.
실대규모 화재시험(ISO 13784-1)을 적용한 샌드위치 패널 시스템의 연소성능 분류
박계원, 임홍순, 정재군, 이길용, 김정욱, 정정호, 이우석, 김운형
1방재시험연구원2방재시험연구원3방재시험연구원4방재시험연구원5방재시험연구원6방재시험연구원7방재시험연구원8경민대학 소방학부
Classification of Reaction-to-Fire's Performances on Sandwich Panel Systems by Applying to ISO 13784-1 Fire Tests
Park Kye-Won, Im Hong-Soon, Jeong Jae-Gun, Lee Gil-Yong, Kim Jeong-Uk, Jeong Jeong-Ho, Lee Woo-Seok, Kim Woon-Hyung
요약
본 연구에서는 ISO 9705(room corner test)에 의한 샌드위치 패널 화재 시험방법을 보완한 ISO 13784-1(room corner test for sandwich panel building systems) 시험방법을 적용하여 샌드위치 패널연소특성 및 성능을 분석하였다. 4종의 샌드위치 패널을 시험체로 선택하였으며, 시험 후 열방출율, 연기 발생율, FIGRA, SMOGRA 결과값을 중심으로 각 패널의 연소 성능을 분석하였으며, 최종적으로 유럽 Eurefic Research Program 및 EN 13501-1에서 제시하는 분류기준에 적용하여 등급분류를 시도하였다.
Abstract
Reaction-to-Fire's performances such as combustion properties of sandwich panels were tested according to ISO 13784-1 (room corner test for sandwich panel building systems) method which is made for the purpose of supplementing ISO 9705 room corner test, and analyzed comparatively. Several variables including heat release rate, smoke production rate, FIGRA, SMOGRA, thermal configuration, visual check lists and so on, were analyzed for specific four materials on sandwich panel systems. Finally, Reaction-to-Fire's performances of test results on each material by ISO 13784-1 are categorized by applying to the classification systems of both EN 13501-1 and Eurefic Research Program.
Key Words: ISO 13784, ISO 9705, FIGRA, SMOGRA, EN 13501-1


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2025 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next