J. Kor. Inst. Fire Sci. Eng. Search

CLOSE


Journal of Korean Institute of Fire Science and Engineering 1993;7(2):24-28.
Published online October 31, 1993.
가연성 액체의 인화점 추정에 관한 실험적 연구
최세환김광일
1대한산업안전협회
2HSB-professional Loss Control
Experimental Study of flash point determination for Alcohols & Aromatic Compounds.
1Korea Industrial Safety Association
2HSB-professional Loss Control
Abstract
The flash point for flammable liquids (alcohol, aromatic compounds) were measured by Penskt-Martens's measuring apparatus with closed cup. As a result, it was observed that the flash points had the regular tendency according to the carbon number and the molecular structure. Consequently, the flash point for the alcohols were increased in proportion to the increase of the carbon number and branch number. The differences between the literature and experimental data are 14.6% for the relative error and 3.46$^{circ}C$ in average for the measuring temperature.
Key Words: Flash Point, Molecular Structure, Fire Source, Heating Speed