Journal of Korean Institute of Fire Science and Engineering 1996;10(2):13-19.
Published online June 30, 1996.
파라핀족과 올레핀족 탄화수소 화합물의 폭발상한계의 추산
하동명이수경
1세명대학교 산업안전공학과2서울산업대학교 안전공학과
Estimation of Upper Explosive Limits of Paraffinic and Olefinic Hydrocarbon Compounds
Abstract
An estimation methodology, based on statistics and numerical method, has been developed for estimating the upper explosive limits(UEL) of paraffinic and olefinic hydrocarbon compounds. With proposed method, the UEL has been calculated for 24 paraffinic and 10 olefinic hydrocarbon compounds. The estimated the UEL agree with the experimental values within a few percent. A comparisond with four other methods avaiable in the literature are also presented. It is hoped eventually that this method will permit estimation of the UEL with improved accuracy and broader application for other compounds.
Key Words: estimation, explosive limits, hydrocarbon