Fire Science and Engineering 2014;28(2):64-68.
DOI: https://doi.org/10.7731/KIFSE.2014.28.2.064    Published online April 30, 2014.
사이클로헥산올의 연소특성치의 측정
하동명
세명대학교 보건안전공학과
The Measurement of Combustible Properties of Cyclohexanol
Ha Dong-Myeong
Dept. of Occupational Health and Safety Engineering, Semyung University
요약
사이클로헥산올의 안전한 취급을 위해, 폭발한계는 문헌을 통해 고찰하였고, 인화점과 발화지연시간에 의한 발화온도를 측정하였다. 그 결과, 밀폐식 장치에 의한 사이클로헥산올의 하부인화점은$60^{circ}C{sim}64^{circ}C$로 측정되었으며, 개방식에서는 $66^{circ}C{sim}68^{circ}C$로 측정되었다. ASTM E659 장치를 사용하여 자연발화온도와 발화지연시간을 측정하였고, 사이클로헥산올의 최소자연발화온도는 $297^{circ}C$로 측정되었다. 측정된 하부인화점과 상부인화점에 의한 폭발하한계는 0.95 Vol%, 상한계는 10.7 Vol%로 계산되었다.
Abstract
For the safe handling of cyclohexanol, this study was investigated the explosion limits of cyclohexanol in the reference data. The flash points and auto-ignition temperatures (AITs) by ignition delay time were experimented. The lower flash points of cyclohexanol by using closed-cup tester were experimented in$60^{circ}C{sim}64^{circ}C$. The lower flash points of cyclohexanol by using open cup tester were experimented in $66^{circ}C{sim}68^{circ}C$. This study measured relationship between the AITs and the ignition delay times by using ASTM E659 tester for cyclohexanol. The AIT of cyclohexanol was experimented as $297^{circ}C$. The lower explosion limit (LEL) and the upper explosion limit UEL) by the measured the lower flash point and the upper flash point of cyclohexanol were calculated as 0.95 Vol% and 10.7 Vol%, respectively.
Key Words: Cyclohexanol, Flash point tester, Explosion limit, Autoignition temperature (AIT), ASTM E659


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next